Devices Panel
ARCO enables you to add Devices to adapt to your system needs.
Keypad
Keypads are used for user interaction to either perform mode changes to an area(s) or to provide feedback to the user for actions on a door. For the case of a door, the keypad can be linked to a reader in the configuration and in this case, the keypad will inherit the properties of the Door configuration for any door actions. There is no need to have any schedules attached to a keypad.
General | |
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Serial Port – Select from the pop-up menu. | |
Device Loop Address – Numerical value. | |
Area – Select from the pop-up menu. | |
Alarm and Card PIN Schedule – Select from the pop-up menu. | |
Limit Area – Toggle ON or OFF | |
Lockout Time – Numerical value in seconds. | |
Invalid Login Attempts – Numerical value. Allowed failed attempts before the lockout. | |
Company Name – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Reporting | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
4G Expansion Card
General | |||
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |||
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |||
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |||
Expansion Slot – Select from the pop-up menu. | |||
Area – Select from the pop-up menu. | |||
Reporting | |||
Report Events – Toggle ON or OFF to record events. | |||
High Priority – Toggle ON or OFF to assign high priority. | |||
Report to – Select the monitoring centre where the data will be sent. | |||
| 4G/GPRS Expansion – Toggle ON or OFF |
| |
Access Point Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. |
| ||
Username – Optional |
| ||
Password – Optional |
| ||
SIM PIN – Optional |
| ||
PDP – Optional |
| ||
Backup SIM – Toggle ON or OFF if secondary SIM is available. |
| ||
Backup Access Point Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. |
| ||
Backup Username – Optional |
| ||
Backup Password – Optional |
| ||
Backup SIM PIN – Optional |
| ||
Backup PDP – Optional |
| ||
| WIFI – Toggle ON or OFF |
| |
Mode – Select from the drop-down menu. Client mode or Hotspot mode. |
| ||
SSID – Provided by the Network Administrator. |
| ||
Password – Provided by the Network Administrator. |
| ||
Security – Select a network security type to connect. |
| ||
Visibility – Select from the drop-down menu. Visible or Hidden. |
| ||
Region – Select a network region to connect. |
|
6 Output Expansion
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Expansion Slot – Select from the drop-down menu. | |
Area – Select from the drop-down menu. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
8 In 2 Out Expansion
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Expansion Slot – Select from the drop-down menu. | |
Area – Select from the drop-down menu. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Aperio
ARCO Platform enables you to monitor and control ASSA ABLOY Aperio devices. Multiple Aperio devices can communicate with one or more hubs using short-distance wireless communications.
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Serial Port – Select from the drop-down menu. | |
| Onboard Isolated – AH-30 Hub is using the PL4-PL5 connection on the S1000. |
| Onboard Non-Isolated – AH-30 Hub is using the PL5-PL6 connection on the S1000. |
Device Loop Address – DIP Switch numerical value. | |
Area – Select from the drop-down menu. Area where the device is located. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Please refer to the Aperio Device Configuration section below for further details.
Audio Board
ARCO Platform enables you to monitor and control Audio devices connected to the S1000 Smart Controller.
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Serial Port – Select from pop-up menu. | |
| Onboard Isolated – Board is using the PL4-PL5 connection on the S1000. |
| Onboard Non-Isolated – Board is using the PL5-PL6 connection on the S1000. |
Device Loop Address – DIP Switch numerical value. | |
Area – Select from pop-up menu. Area where the device is located. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Please refer to the Audio Configuration section below for further details.
Audio Converter
ARCO Platform enables you to monitor and control Audio devices connected to the S1000 Smart Controller.
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Expansion Slot – Expansion slot where the Audio Converter is installed. | |
Area – Select from the drop-down menu. Area where the device is located. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Please refer to the Audio Configuration section below for further details.
CRI Expansion
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Expansion Slot – Expansion slot where the CRI Expansion is installed. | |
Area – Select from the drop-down menu. Area where the device is located. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Card Reader Interface
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Serial Port – Expansion slot where the device is installed. | |
| Onboard Isolated – Board is using the PL4-PL5 connection on the S1000. |
| Onboard Non-Isolated – Board is using the PL5-PL6 connection on the S1000. |
Device Loop Address – DIP Switch numerical value. | |
Area – Select from the pop-up menu. Area where the device is located. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
DVR
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
RTSP URL – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
RTSP URL (recorded video) – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. |
Ethernet Expansion
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Expansion Slot – Expansion slot where the Ethernet Expansion is installed. | |
Area – Select from the drop-down menu. Area where the device is located. | |
Expansion Ethernet – Select from the pop-up area. | |
| – Leave Existing – ARCO will not download any Expansion Board Ethernet settings. The settings programmed using the keypad or mobile app will be retained. |
| – Enable – Input ethernet configuration. |
| – Disable – Disable Ethernet port on the expansion board completely. |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
IDIS DVR
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
RTSP URL – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. |
Inovonics
ARCO Platform enables you to monitor and control Inovonics EchoStream devices. Multiple Inovonics EchoStream devices can communicate with one receiver using wireless communications.
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Area – Select from the pop-up menu. Area where the device is located. | |
Product Type – Select from the pop-up menu. | |
| – Serial Receiver – Select to configure the receiver first |
| – Transmitter – Select to configure a device that transmits input signals |
| – Environmental – Select to configure a device that monitors the environmental status |
Product Model – Select from the pop-up menu. Model of the Inovonics device. | |
Serial Number – Normally this is on a sticker on the device, or maybe on a sticker inside the cover | |
Parent – Select a Controller as parent | |
Offline Timeout – Numerical value. | |
Signal Change – Numerical value. | |
Signal Minimum – Numerical value. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Please refer to the Inovonics EchoStream Configuration section below for further details.
Modbus
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Serial Port – Expansion slot where the device is installed. | |
– Onboard Isolated – Board is using the PL4-PL5 connection on the S1000. | |
– Onboard Non-Isolated – Board is using the PL5-PL6 connection on the S1000. | |
Device Type – Select from the pop-up menu. | |
Area – Select from the pop-up menu. Area where the device is located. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
OSDP Reader
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. Unique identifier assigned to a device connected to the S1000 Control Panel. | |
Serial Port – Select from the pop-up menu. | |
Device Loop Address – Numerical value. | |
Area – Select from the pop-up menu. | |
Access Schedule – Select from the pop-up menu. | |
Company Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
PSTN Expansion
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Expansion Slot – Select from the pop-up menu. | |
Area – Select from the pop-up menu. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Remote IO
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. Unique identifier assigned to a device connected to the S1000 Control Panel. | |
Serial Port – Select from the pop-up menu. | |
Device Loop Address – Numerical value. | |
Area – Select from the pop-up menu. | |
Expansion 1 – Select from the pop-up menu. | |
Expansion 2 – Select from the pop-up menu. | |
Expansion 3 – Select from the pop-up menu. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Sensor Board
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Expansion Slot – Select from the drop-down menu. | |
Area – Select from the drop-down menu. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Third Party Alarm Panel
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Serial Port – Select from the pop-up menu. | |
– Onboard Isolated – Board is using the PL4-PL5 connection on the S1000. | |
– Onboard Non-Isolated – Board is using the PL5-PL6 connection on the S1000. | |
Panel Type – Select from the pop-up menu. | |
– PACOM Alarm Panel | |
– Honeywell Vista Alarm Panel | |
Area – Select from the pop-up menu. Area where the device is located. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |
Third Party Sub Device
Name – Needs to be unique for each controller. Requires alphanumeric characters with no spaces with a maximum length of 255. | |
Description – Requires alphanumeric characters with a maximum length of 255. Does not need to be unique. | |
Logical ID – Numerical value. The unique identifier assigned to a device connected to the S1000 Control Panel. | |
Remote Logical ID – Numerical value. The unique identifier assigned to a device connected to the Third Party Alarm Panel. | |
Device – Select from pop-up menu. The Party Alarm Panel this sub device is connected to. | |
Area – Select from the pop-up menu. Area where the device is located. | |
Report Events – Toggle ON or OFF to record events. | |
High Priority – Toggle ON or OFF to assign high priority. | |
Report to – Select the monitoring centre where the data will be sent. |